Performed AC tuneup on 2007 carrier heatpump. Upon my maintenance there were a few points of concerns that were addressed with The homeowner. Carrier condenser- 1. Found that single secondary motor control the powers fan has become weak reading at 4MFD when our reading should be at 5 MFD. The weaker the battery gets the more strain and damage it causes to the component that it powers. 2. Dual secondary motor control that powers compressor was also at 36MFD when it’s actual reading should read at 40. 3. High voltage relay had a bit of pitting/burnt on contact points. 4. Condenser fan motor showed no signs of oil leakage in spinner freely. 5. Refrigerant pressures for R410a we’re in range 6. Amperages were in range at this moment 7. Condenser coil was cleaned off and ready for summer 8. Air handler on side of home had no return plenum on tops. Also filter needs to be swapped every one to three months For best filtration 9. Drain lines were cleared and we’re properly draining Discu