Upon arrival performed diagnostic. System is throwing out a e312 code. Client says between times of 11-3 system doesn’t work. System has been running & cooling. Found return is very undersized for 5 ton system. Only have about 1200 cfms on a 5 ton system. Ducting is original. Freddy to come out and asses ducting. System is operational as I’m here and as I leave.
Upon arrival performed diagnostic. System is throwing out a e312 code. Client says between times of 11-3 system doesn’t work. System has been running & cooling. Found return is very undersized for 5 ton system. Only have about 1200 cfms on a 5 ton system. Ducting is original. Freddy to come out and asses ducting. System is operational as I’m here and as I leave.
Upon arrival performed diagnostic. System is throwing out a e312 code. Client says between times of 11-3 system doesn’t work. System has been running & cooling. Found return is very undersized for 5 ton system. Only have about 1200 cfms on a 5 ton system. Ducting is original. Freddy to come out and asses ducting. System is operational as I’m here and as I leave.
Upon arrival performed diagnostic. System is throwing out a e312 code. Client says between times of 11-3 system doesn’t work. System has been running & cooling. Found return is very undersized for 5 ton system. Only have about 1200 cfms on a 5 ton system. Ducting is original. Freddy to come out and asses ducting. System is operational as I’m here and as I leave.