Jimmy P.

Jimmy P.


Job Checkin

Performed AC diagnostic on 1989 condensing unit. Upon my diagnostic I found that the condenser fan motor was running although compressor was not and then proceeded to open up the service panel and found that the battery cap hermetic side terminal was blown. Replaced battery cap And Compressor became Energized. Measured refrigerant pressures although system did contain our 22 band Freon pressures were adequate with 59° supply temp when indoor temperature was 87. Recommended that compressor Is replaced if they want to stop experiencing intermittent behavior because once I was done and the new battery cap was in the compressor did fail on thermal overload. This compressor is a failing compressor and will completely not work soon. Also recommend a compressor starter kit to reduce lock rotor amps on start up and then high-voltage relays replaced due to high amounts of pitting on contact point. Upon departure system was running although it’s going to be intermittent due to the windings on