Arrived on site to diagnose a no cooling 1986 inner therm system. That is not cooling or operational. Upon arrival spoke over with client and stated system was cooling yesterday and system no longer turns on or cools. Found indoor u it on and has power. Found out door unit not operational. Advised client I will inspection g out door unit. The summary of findings are as followed Condenser 1. 1986 Intertherm system. 2. Condenser not operational upon arrival. 3. Found fan motor completely covered in oil from leaking in past. 4. Secondary motor control for compressor and fan motor are both out of range from components over working and draining life of secondary control. 5. Found disconnect fuse popped and not allowing power to enter condenser. 6. Compressor is burnt up as it will not operate or turn on. 7. Compressor tripping breaker switches as it is bad now creating g a short to trip breaker. 8. R-22 refrigerant used that’s no longer in production and has been phased out by EPA. W