Tech arrived on site. No airflow throughout the house. Got attic access and found the motor controller had failed. Installed new motor controller to test motor. The motor is operational. Found the return duct to have collapsed internally from unknown causes. Was able to force the duct open. Unit is getting better airflow now. Also found burn marks on control board. The board might fail soon. It’s still operational now. Tested outdoor start components. Found the dual secondary motor controller to be weak but within range. Compressor drawing high amps. Recommend budgeting for replacement soon. Client signed up on maintenance program. Did first visit tune up while on site. Unit is operational upon departure.