41638 Eastman Dr. Suite B
Murrieta, CA 92562
(888) 659-2665

Job Locations
for la verne, ca


Map of La Verne CA
Jorge C.

Jorge C.


Job Checkin

Performed diagnostic on 3 year old furnace. System is not heating. Cycled system for heating. System initiated heating sequence , but pressure switch failed to close. Found pressure hose was ripped or possibly chewed through by rats. Repaired hose and cycled system. System went through proper heating sequence of operations and started heating. Filters on both units extremely dirty. Replaced both filters with approval. Cycled system. System is fully operational upon departure.