Arrived on site to perform fall tune up a 2013 carrier system. Furnace furnace located in attic client stated no issues. Cycled nest thermostat and was good and operational. Found filters dirty and client was goin got go buy and supply his own. Found black flex ducting used and visually inspected system and found a big tear where the plenum meets the furnace is torn and leaking dirt into system bypassing the filter. Recommend resealing return plenum to stop dirt from entering from the attic. Blower assembly and wheel is dirty creating stress and wear on motor. Motor has slight oil developing from over Working and stress allowing dirty to accumulating with the oil. Would recommend replacing blower motor to extend system life span as it starting to show Signs of premature failure and if fails airflow will not be produced in heating and cooling. Secondary motor is good and in range. Inspect Heat exchanger and found heat impingement and is good at this time. Inducer motor is amping at 1.0