41638 Eastman Dr. Suite B
Murrieta, CA 92562
(888) 659-2665

Job Locations
for lake elsinore, ca


Map of Lake Elsinore CA
Daniel T.

Daniel T.


Job Checkin

Performed furnace maintenance on a Lennox Furnace in Lake Elsinore. Systems temperature split is 38 degrees. Combustion blower is amping under max spec. Flame sensor was cleaned and Reinstalled. Unit is equipped with a germicidal light which is still glowing strong at this time. Merv 16 filter is dirty for only being 4 months old. Ignitor is reading high but still in range at this time. Blower wheel is spinning freely. Performed A/C maintenance on a Lennox XC25. Condenser coils were heavily caked with dirt. System was chemically washed and rinsed. Cooling temperature split is right at 20 degrees. Systems control and defrost board are clear of any visual burn marks. Compressor is amping within range. Fan motor is amping under the max for this unit.