Arrived on site to perform diagnostic on 10 year old unit. Met with Michael. On arrival, Michael let me know that he was the tenant, verified that we had homeowner permission to be on site to which he said he had homeowner permission. Depending on repairs Michael will be taking care of payment and then taking care of it with homeowner. Thermostat is black and cooling is not working. Checked for power at thermostat and there is no power coming to thermostat. Went into attic and found furnace had a blown fuse. Replaced fuse and immediately blew again. Checked wiring and found the wire going to the condenser to be shorted out. Wire to condenser Needs to be rewired. With Michaels approval went ahead and re wired low voltage command from condenser and furnace. Upstairs Thermostat now has power and unit is cooling. Michael did let me know that unit has a leak at the evap coil that has been diagnosed by another company. They fill the refrigerant once a year. I checked pressures and they are