Arrived on air w to perform spring tune up on a 2011 unit. Condenser located on side of home furnace in closet. Client stated no issues and cycled unit. Washed condenser coil inside and out. Primary starter is pitted on points and old. Secondary motor control is out of range on fan as it was as well last year. Recommend replacing. Fan motor is leaking oil and is over amping pulling 1.4 and max at 1.1. Checked start up and run amps on compressor. Run amps pulling 10 and max at 18. Those can go up when it get really hot outside. Recommend a booster kit for compressor to preserve it from a hard start up and stress. Checked pressure and unit is holding charge and cooling hole at 21 degrees. No protection on unit. Filter was dirty and blowers as well. Motor leaking oil from age and past use. Could fail in future. Only has one drain line and not good as there is no safety overflow switch if lines were to get clogged. No protection on I for unit. Cycled unit and not and went over all findings