Call was for low airflow in daughters room. Got on site and performed system evaluation. Found issues of concern. High static pressure found the system not getting enough airflow. Not enough return air. Supply ducting is not sized properly. Charge indicated it was low. The filter was also restricted. The most economical way to get airflow to daughters bedroom is to put a damper on the laundry room supply vent. Cutting off airflow and forcing more into her vent. This will cause more noise in that vent. It’s recommended to do additional ducting modifications to have the system performed the best. Made recommendations. Sent email. Recommend doing system tune up and cleaned coils and replacing filter, then recheck charge to see if it’s actually low. Performed leak check on evap coil while on site. Did not find anything. System is operational upon departure.