Mandatory Client reports that he had a service done about a year ago and the tech advised that their cap was going out. Findings: (1) Found cap to be dead on the hermetic side. (2) The old cap’s data label was rusted out and could not read the proper size. Inspected the other units cap and its label was also rusted out. Checked energy levels of that cap and found it to be a 45 size. (3) Installed a new cap and tested system operation. (4) Found the compressor to be consuming a lot of energy at start up. The compressor needs a hard start kit. (5) The fan motor is over amping during operation. This should be replaced or failure will occur. Notes: (1) Client declined additional repairs being done. (2) Client declined the membership at this time. (3) The system is operational upon departure