Upon arrival found 1 2 year old heater. Insulation was inside the burner cabinet. Cleaned up system. Tested it in heating mode. Electrical components are in good condition. All motors are in operational range. Flame sensor was cleaned. Found system static pressure was higher than its rating. Duct system is undersized and under insulated. Other than that unit is operational upon departure.