Arrived on site to perform AC diagnostic on 1979 condensing unit. Upon arrival Sylvia was present and explain that the unit was operational and all the sudden two days ago and just shut off and no longer blowing any air. Started at Indoor Furnace and found that there was no low voltage power present. Measured low voltage power coming off of transformer and found that transformer has become defective and is no longer sending out 24 V. Indoor unit was an extremely bad shape it looks like it has not been maintenance in years. Indoor blower motor had oil leakage coming off of its bearing. Transformer has been replaced twice already as well. Proceeded to outdoor condensing unit and found that disconnect was in upside down position. Unit fired up and I began to measure refrigerant pressures. System did not look to be in good condition and found that refrigerant pressures were low along with the suction side Schrader core been jammed and stuck inside. By measuring the suction line temperature