Performed diagnostic on 2 2006 Rheem units. Homeowner states that both units are blowing air, but not cold. Neither of the outdoor units are turning on. One has been down for a while, the other stopped working last week. They did have a power outage around the same time that unit stopped working. Cycled units for cooling. Indoor units both kick on, outdoor units is not operational. Outdoor Systems are both extremely dirty And need some cleaning and maintenance done to them. Diagnosed both systems, findings are as follows; UPSTAIRS UNIT: 1. Upstairs unit was not recieving any high voltage power. Found a tripped breaker that was not allowing system to kick on. Reset breaker and unit kicked on. Amp draws are within range for compressor. Amp draws on condenser fan motor are slightly high, and motor has leaked out a lot of oil. Refrigerant pressures are in range and system is producing proper temperature split. Indoor Filter was extremely dirty as well as condenser coil. DOWNSTAIRS UNIT: