41638 Eastman Dr. Suite B
Murrieta, CA 92562
(888) 659-2665

Job Locations
for san jacinto, ca


Map of San Jacinto CA
Jimmy P.

Jimmy P.


Job Checkin

Performed AC diagnostic on 2005 Brian Condenser. Upon my diagnostic client Stated that system would not drop below 90° in the house. They believed that the system was old and may need to be replaced although I wanted to see what was going on with it first to verify the full condition of it. Heater is from 1984 and Ac is from 2005. Systems are way past design life and showed many terminal faults. Upon arrival I found out the outdoor unit was not kicking on due to the duel secondary motor control becoming defective. 1. Duel secondary motor control was defective on both compressor and fan side terminals due to Compressor using too much power over time. 2. Compressor is pulling 8 A when it is only rated for 11 A. This unit may becoming very close to over amping And put the system at a higher risk of failing once this happens. 3. Starter showed signs of pitting on contact points due to high Amperage. 4. System Contained R22 refrigerant which was phased out January 1, 2020. 5. Condenser fan