Performed diagnostic on 2003 Payne unit. Homeowner states system is not blowing any air at all inside the home. Cycled system for cooling. Outdoor unit kicks on, indoor unit is unresponsive. Checked system electrical and system components. System is recieving proper voltage. Thermostat is sending proper command to circuit board but indoor fan is not turning on. Secondary motor control for indoor fan still in range. After testing, found that circuit board is not sending power for the fan to kick on. Circuit board needs to be replaced. Tested fan motor separately with pig tail and motor kicks on so motor appears to still be good. Can not perform thorough evaluation of system until circuit board is replaced. Went over findings and recommendations with homeowner. She wants to call her home warranty and see if there is anything that can be done or if they can give her any money for the repairs. System was left non operational upon departure.