Jimmy G.

Jimmy G.


Job Checkin

Arrived on site to perform fall tune up on 2 2009 carrier furnace. Both Furnace located in attic. Client stated no issues. Cycled heating mode on on both. Both systems operational. Advised client I would be inspecting proper operation and efficiency and safety as well. Advised the summary of findings are as followed. Downstairs furnace 1. 2009 carrier furnace. 2. Found black flex ducting used and in ok condition. 3. Furnace Airflow is restricted as not enough airflow is entering system. 4. Filters are dirty and client supplies and replaces his own filters. 5. Blower assembly and wheel has dirt build up creating stress on motor. 6. Motor is now leaking oil and starting to leak oil in wheel from over working. Motor is pulling 7.1 and max rated at 10. Just indicating motor is working hard and if continues motor could possibly fail in future. 7. Secondary motor control is now weak. Recommend replacing before component completely fails and motor will not operate in heating and cooling.