Arrived on site to diagnose a noise complaint on a 1 year old lennox unit. Client stated unit si brand new and didn’t make this noise in past or when installed and just the past couple days started. They just wanted to ensure nothing is going on with unit. Cycled on and heater turned on and once blower motor started is sounded like a whistle noise advised looked into return vent and didn't see anything. Inspected attic and return plenum And filter rack. Found the tape on the outside sealing up connections from plenum and rack the stale had came lose and cause the noise as it’s sucked air. Pressed back ona no noise stopped. Sealed up return and filter rack with more tape to seal up the lose tape and noise had completely stopped. Showed client the noise and what caused it. Unit is operational and heating home and noise is gone. Cycled unit and unit is operational upon departure.