Arrived on site to diagnose a no cooling system 1999 carrier system. Condenser located in back yard. Furnace located in garage. Spoke to client upon arrival. He stated system was working fine 2 days ago then Suddenly stopped. He went and saw out door unit was not operating and fan not spinning as no cool air was being produced. Had client cycled cooling mode. Indoor unit turned on but condenser was not operating. Advised client I would be inspecting indoor and out door unit. Checking electrical wiring, connections, circuit board, and components. Checking fan motor and blower motors and blower assembly. Inspected amp drawls of motors and compressor. Checking Refrigerant pressure and cooling temperature split.advised the summary of findings are as followed. Condenser 1. 1999 carrier condenser. Found don’t operation upon arrival. 2. Condenser unit was really dirty and clogged up creating airflow restriction to out door unit Causing it to work harder to remove heat in home. 3.Prima