Arrived on site to diagnose exposed thermostat wires on unit. We were last out and did repairs. Upon arrival found unit operational. Client was just concerned due to the chewed up exposed thermostat wires and would like to ensure system is operational and no issues would occur. Found low voltage thermostat wires chewed up and exposed. Which is not replayed to the repairs done in past. Advised client we can repairs low voltage wires and get system operational. Client is aware system is operational just wanted to ensure wires wouldn’t cause any damage to system. Client approved to go forward with repairing low voltage wires. Cycled system to ensure system operating. Checked amp drawls on compressor and fan motor. Found compressor is having high start up as it’s pulling 51 on start up and max rated for 64. Recommended adding a compressor booster kit to help reduce high start up and help preserve compressor and prolong ice of unit it self. Client did declined other recommended work a