Antelope California heating AC service AC maintenance AC diagnostic AC not working no cool air AC diagnostic findings system trying to run / cool not working house is 87° inspection at outdoor unit found compressor overheated Open winding terminals. outdoor fan running has very bad vibration. causing top panel to start cracking will continue to damage top that is holding fan motor in place due to vibration. capacitors found bad compressor capacitor likely cause of compressor overheating do to system trying to run and not working possible damage to compressor has occurred. Repairs needed compressor called off to try and see if windings will open if windings do not open compressor will need to be replaced if windings open next step would be to replace capacitor. Replacement of capacitor needed to be able to test system operation. Cooled compressor down replaced capacitor turned on system checked operation blower capacitor still weak could go out at anytime and keep the blowe