Performed annual ac maintenance auburn. 26yr old gas package unit back yard. Found 20-20-1 filter dirty. Changed filter. Gave unit a bath cleaning coils. Found contactor working, just pitted and burnt. Dual capacitor ok, for now it’s in range, due to age can’t say when it will fail. Compressor weak but working. High side seems higher than temperature should be. Could just be unit design. System is old and inefficient, but working for now. Found leaking Schroeder valve. Made sure cap is on tight and not leaking for now. Low voltage wire not in a whip. Client wants to renew membership come winter visit.