Connect line sets to ductless mini split system 4 indoor heads 1 outdoor condenser 8 connections total. use proper flaring block with digital torque wrench. torque to proper manufacture specifications, pressure test system, vac system to below 450 microns and start up unit charge if necessary. Customer requested to remove duct testing as he is scheduling direct with Valley Duct Testing.