Got to unit running, making extra noise. Hooked up gauges system still holding refrigerant. Compressor looks to be weak. Found disconnect hot to touch, checked electrical all appears tight and ok at this time. Turned system off and cooled off unit with hose. Tried to run system again, system ran like normal for a few seconds then you can hear the bypass opening. Tried to pump down the system at 90 psi compressor bypass opens up, weak compressor. From here a compressor is 7-14 days from factory. Condenser and coil, openings next week.