Job Checkin

Performed annual heating maintenance loomis, rheem upflow under house. Tested zoning system working at this time. Cleaned burners and flame sensor, burners pretty rusty. Gas pressure ok. Tested inducer capacitor 4@3.9. Tested blower motor capacitor 15@12.7. Recommend replacement out of manufactures recommend specs. Electrical connections good, board looks good no burn marks. This is the unit that had the cracked exhaust pipe and was leaking. Ducts mix of black and silver flex. Filters electromaze washable, washed all of them. blower capacitor for zoned system 15@12.7 Blower capacitor for horizontal system 15@12.8 Inducer capacitor for horizontal system 4@3.4 Thermostat for horizontal system button not working correctly.