Meadow Vista California heating AC service heating AC maintenance heating AC diagnostic HVAC replacement. Performed AC maintenance bedroom / downstairs unit - turned the unit on to check operation of system turned on / running with no problem. Checked refrigerant pressures good, checked amp draws compressor 7.56 , outdoor fan 1.1 good, capacitors 80/5 reads 82.1/3.9 Condenser fan capacitor out of manufacturers tolerance +/-6% =+/- .3, Visual inspection of electrical - wiring good no burnt or overheated wire connections, Service disconnect wires tight, contactor - contact points normal wear. electrical megaohm test - unit passed. performed simple water wash of condensing coil and flushed condensation drain line part of AC maintenance Unit operating Repair replaced condenser fan capacitor