Came out for diagnostic for downstairs unit. System turns on outside and runs but there is no airflow to downstairs part of house. Checked all electrical in attic and found that the capacitor in the downstairs furnace was about 30% below it’s recommended rating. Showing 3.11uf and should be no lower than 4.8uf. Checked blower motor to see if it was okay and is grinding and not spinning freely. Informed customer that this was a hazard and unplugged unit until repairs can be done.