Keaton R.

Keaton R.


Job Checkin

Upon arrival I noticed that unit was inaccessible to service. Trees and bushes have grown over unit and cannot get access to service side of unit. Homeowner is going to trim bushes today so i am able to access and service unit. Bushes are somewhat clear now, still limited access to unit but enough to service. Performed a.c maintenance in Sacramento. Unit is a Goodman condenser in side yard. Unit has a lot of debris inside and outside unit. Has 240v going to unit. 50amp breaker in breaker panel. Checked electrical connections and are okay but have a lot of spider webs and dust inside compartment. Checked capacitor and is in range 42.2/4.9 and should be at 45/5 +-6%. Coils are clean on unit only some leaves at bottom of coil. Amp draw of fan is .44amps and is okay. Amperage draw of compressor is 6.27amps and is okay. Will brush off dust inside of electrical compartment. Refrigerant levels are showing for R22 is showing 58psi Lowside and 194psi Highside. Temperature inside is 76 degree