No heat, found furnace running upon arrival, check heater operation and test ok check errors on history found E0 ignition lock out, check all electrical, ground wire ok, check pressure switch and tubing ok, could not get furnace to failed did not din any issues, talked to Amana Rep, and he recommend to check heat exchanger for any leaks, inspect exchanger found lot of areas with rust, looks like condensation is getting to exchanger, could not check exchanger with my camera we will need a High definition camera and try to inspect heat exchanger deeper, return visit is need to check heat exchanger