Install an EZ Trap onto the Condensation Drain Line for the AC system. Adapt to existing drain line. Wire EZ Trap in series with the Condensation Pump to break the 24V control circuit of the system. Move ceiling panels to access and remove existing vinyl tubing. Install new Vinyl tubing for the Condensation Pump. If an indoor discharge is available run tubing to an indoor pipe. Current tubing appears to be running to the outside. 8/3/20. Installed new ez trap and ran new vinyl hose to drain behind system. Connected low voltage wiring to break the “r” terminal inside furnace. Re connected to the condensation drain and ran system and checked for water leaks, no leaks. System is working fine at time of service.