Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.
Found 45/5 capacitor tested at 42/4.3 mfd recommend replacing. Replaced capacitor. Also performed precision a/c tune up on amana and York a/c systems. Checked all electrical conections and components. Blew out condensate drains. Checked temperature splits. Checked refrigerant pressures and temperatures at indoor and outdoor units. Both a/c systems are working fine at time of inspection.