Service call that the relief valve was leaking water heavily. Upon arrival, hooked up Pressure Gauge to the boiler and found Pressure at 30-35 PSI and water was steadily coming out of the Relief Valve. Checked Expansion Tank and found expansion tank was full of water. Drained Expansion Tank of water and adjusted pressure on the Boiler to 15 PSI. After a relief Valve opens it may not fully close and continue to leak water due to not fully seating back in the closed position. If this occurs, then the relief Valve will need to be replaced again.