Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.
Water leak, found 3 to 2 in reducer leaking on of the joints, will need to replce 3 to 2 in reducer and also will need a 2 in coupler, during testing noticed insid heater cabinet getting hotter than normal, start heater and defrost combustion test with blower on and off, co went over 100 with blower on when blower off goes down to 10, remove limit and inspect ex charger not visual propblem, but you can see flame/light from inside limit, heater should not be runninglike that, turned gas off and electrical, explained customer about situation, once I leave is up to customer to turn heater back on, quote for new exchanger recommend new heater