Service call that the Boiler was not firing. Spoke with Landlord upon arrival about issue. System was set to heat but the Oil Burner was on a Hard Lockout. Turned system off and inspected. Was unable to remove the Oil Filter because the shut off valve on the Oil Line is after the Oil Filter. Checked Nozzle and Electrodes. Checked Oil Pressure through the pump and found no Oil Flow. Removed the Oil Strainer and found it was completely clogged. Replaced Oil Strainer and Oil Nozzle. Cleaned and set Electrodes. Put system back in operation and tested. Performed Combustion Analysis, Smoke Test, and Draft Test. Found Water Pressure higher than normal. Bled some water from the system to reduce pressure. Would recommend replacement of the Water Fill Valve and the Expansion Tank to insure that the water pressure does not increase higher than recommended. Also recommend Installing a Shut Off Valve before the Oil Filter. Currently there is no way to shut the Oil Off and replace the Oil Filter