No ac found system off upon arrival set thermostat to call for ac and found compressor not running making humming sound three phase compressor, switch two leads at contactor and compressor came on cycle couple times compressor came on, monitor ac cycle, compressor amps at 10 amps, replaced filter, adjust charge r22 system is working in poor condition only 12 degree split, System will not work properly when outside temp is above 90 degrees, today’s readings outside temp 84...pressures 210/70 with liquid line temperature 87 suction line temp 68,.,,supply temp 60 return air 73, 15 sub cooling and 29 super heat, system is at maximum output