Luis T.

Luis T.


Job Checkin

Performed ac tune up, system is set up for zoning two zones not sure if it’s first and second floor, zoning panel has two thermostat inputs and two zoning damper outputs zone 1 and zone 3. On zone 1 two dampers 10x24 are tide in in zone 1 contacts, tried to look zone 3 damper could not see based on customer information second floor thermostat controls zone 3 did not find zone 3 damper, or of the 10x24 dampers is not opening 100% would recommended replacement of that damper right side of unit by humidifier, check operation of system replaced filter flushed drain test pump check airflow ok good temp split inside temp is 65 no load inside the house, check outdoor unit refrigerant pressures 200/60 suction line temp is very cold due to to low temp inside the house, pressures look ok based on indoor and outdoor temp, capacitor ok contactor should get replaced emailed proposal for recommendations on new contactor and zone damper