Water leak coming from ac indoor coil, inspect drain and flushed drain ok, no problem with drain, check filter ok check refrigerant pressures, customer had compressor replaced this summer and was converted to R438A refrigerant slightly different pressure differential, new compressor is rated at 45 degree coil temp, check super heat and subccoling 200/55 with 30 superheat and 11 subccoling calculated target superheat, target is 12 with outdoor temp and indoor wetbul temperature relation, system is low in refrigerant