Six month inspection for 100,000 BTU 2 stage Amana furnace and AC system. Heating temp rise 45F. Cooling temp split 17F. Cleaned EZ trap verified drain. Cleaned flame sensor. Visual inspection of burners and heat exchanger ok. Combustion test good. Compressor amps/outdoor voltage/outdoor capacitor ok. Both heating and cooling system are operating well at the time of this 6 month inspection.