Checked no cooling on new air conditioner, found no call to Y only the Blower comes on, found an open Y wire from the thermostat to a splice and to the furnace. Temporarily jumped Y and G at the splice to run cooling. A wireless thermostat or 2 or 3 wired thermostats are the only option without trying to pull a new thermostat wire to the second floor. I explained that they can not run the fan in the on position only auto until thermostat wire issue is fixed.