Service call that the Heat for the Second Floor System was not working. Arrived onsite and spoke with Homeowners about issue. Found Thermostat set to 74 Heat and the Indoor Temperature was 68. Proceeded to the Attic to diagnose. Found that the Control Board was not receiving the Voltage signal to turn the Heat On. Tested Control Board and Thermostat and determined that the Thermostats internal contacts had failed. Installed a new Honeywell T6 Pro Thermostat. Programmed Thermostat and tested operation of system. Reviewed the Thermostat programming and use with the Homeowners.