Service call that the Heat for the Second Floor was not working. Arrived onsite and spoke with Homeowner about issue. Found Second Floor Thermostat was calling for Heat. Proceeded to the Furnace in the Attic to troubleshoot. Furnace was displaying a 3 Flash Code indicating a Pressure Switch issue. Cycled Furnace and found that the Inducer Motor was not turning on. Tested Voltage, and the Inducer Motor was not receiving Voltage to turn on. The Control Board was not sending the correct Voltage and the was immediately locking out in a Pressure Switch Error Code upon start up. The Control Board is failing and needs to be replaced. There may be further issues with the Furnace that cannot be determined at this time until the Control Board is replaced. We will order the Control Board in the morning and follow up to schedule the repair based upon availability of the Board. Returned to replace Control Board. Removed faulty Board and installed new Control Board. Rewired Control Board into sy