Performed cooling maintenance on 3.5 ton heat pump. Checked media filter found dirty and needs to be replaced. Cleaned condensate drain and pump. Tested condensate Pump. Checked voltage, amperage and electrical connections. Measured capacitor values. Started heat pump, measured refrigerant charge, found low on charge. System outdoor is 11 years old matched to an older air handler. Recommend replacing system vs repairing fur to obsolete R-22 refrigerant.