Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.
No ac, customer has been resetting breaker, check outdoor operation and found code 04 on history, locked rotor, could be that at some periods of time there is voltage dropped, and board sees that, installed potential relay 5-2-1 terminals and also start capacitor to over come voltage issues, also will provide better starting torque, no charge