Heat Tune up 100K BTU 2-stage propane furnace. Checked filter; ok Checked humidifier pad, opened bypass damper @ plenum, verified humidifier operation. Checked burners, heat exchanger, flame sensor and hot surface ignitor. Measured temperature rise. Checked static pressure (ductwork). Checked gas pressure (inlet, HI Fire, LO Fire). Checked pressure switches and components. Checked all electric motors and components. Combustion/draft test: Good. Furnace is operating well at the time of this maintenance.