Performed precision a/c tune up on Rheem a/c system. Replaced 16x20x1 air filter. Checked all electrical conections and components. Installed ez trap in attic and tested a/c drain. Checked temperature split at air handler. Tested outdoor capacitor. Checked refrigerant pressures and temperatures. Found high head pressure due to very dirty outdoor coil. Recommend cleaning outdoor coil. Washed off outdoor coil and re-checked refrigerant pressures are now ok. A/c system is working fine at time of service.