Service call that the Air Conditioning was not working properly. Upon arriving, found Thermostat was set to 63 Degrees and the Temperature within the home was 77 Degrees. Temperature differential was at 10 Degrees. After troubleshooting system, found Compressor was completely frozen and the Indoor Coil was frozen. Defrosted both the Indoor Coil and the Compressor. Put system back in operation and tested Refrigerant. System was low on refrigerant which was causing it to freeze. Added 3lbs of 410-A Refrigerant to system. Monitored system, and charged unit using Superheat Guidelines. Upon completion temperature Split was 18 Degrees. Replaced the 20x20x1 Air Filter. Set Thermostat to 72 Degrees. Performed a quick leak search using the UV Light, and was unable to find a source of the leak at this time. Due to no one being home at this time, the Office will follow up for payment.