Performed Precision Heating Tune Up on Propane Fired Furnace. Replaced 16x25x1 Air Filter. Inspected Electrical Components on Furnace. Cleaned Furnace Drain Lines and Condensation Pump. Inspected Burners and Flame Sensor. Flame Sensor has minor pitting beginning to form. Cleaned Sensor and it is still in good condition. Due to the moisture and corrosiveness of the Propane, the Flame Sensor will likely need to be replaced every 2-3 Years to ensure no issues with the Heating. Performed a Combustion Analysis on the system. Furnace is operating to standards at this time.