Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.
Tuesday 10/27: Returned to site and installed new Control Board. Completed all wiring connections. Installed new ECM Motor Surge Protector and completed wiring. Started system and Control Board was displaying B1 Error Code. Removed Blower Motor and inspected Module. Found Blower Motor had also been damaged in Power Surge and will need to be replaced. Will order new Blower Motor and schedule return visit to replace. Monday 10/26: Service call that the Heat was not working. Was informed that they experienced a power surge and the system stopped working after that. Found thermostat display on. Set thermostat to heating to test. Found no display on the Air Handler Control Board. The outdoor unit was running but the indoor unit was not operation. Also found ECM Motor surge protector had blown. Removed surge protector and directly plugged the Motor back in. The motor was receiving the correct High Voltage but the Control Board was not sending out any low voltage to the motor. The Control