Found that up in attic furnace blower was running but not outside unit. Found 240 volts passing thru contactor but nothing was running. Found blown 40/5 mf capacitor. Replaced capacitor and checked r-22 refrigerant pressures at 88 degrees outside temp. They were 215/72. Checked temperature split at indoor unit and had a 20 degree temperature split. System is working fine at time of service.